The complete list of active alarm codes for the Carrier APX control system used on X4 7300 / 7500 and X2 trailer units, grouped as in Carrier’s APX Alarm Guide (62-12130): the code, the alarm name as the MessageCenter shows it, whether it shuts the unit down, and Carrier’s recommended action. Most alarms point to a sensor, a circuit or the refrigeration system. The microprocessor, communication (NO COMM) and board alarms are the ones that can mean the controller itself has failed — and those are the modules we repair.
Common Failure Symptoms We Fix
Microprocessor Alarms (00232–00255)
NO COMM Alarms Between Modules (21100–25100)
Board Alarms (INPBD1, OTBD1, STP)
Our Repair Process Includes:
- 441 Active APX Alarm Codes
- Shutdown vs. Alarm-Only Response
- Carrier’s Recommended Action for Each Code
Complete Carrier APX alarm list (441 codes)
Alarm names are shown exactly as the unit’s MessageCenter displays them. “Restart” and “Reset” mean placing the START/RUN-OFF switch in OFF, then back in START/RUN.
Driver Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 00001 | Low Fuel Level Warning | Alarm only | Add fuel; the alarm clears |
Shutdown Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 00011 | Check / Low Engine Oil Pressure | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00012 | High Coolant Temp | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00013 | High Pressure | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00014 | High A/C Amp | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00015 | High Battery Voltage | Shutdown | Report and repair immediately |
| 00016 | Low Battery Voltage | Shutdown | Report and repair immediately |
| 00017 | High Discharge Temp | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00018 | Low Pressure Shut Down (Suction) | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00019 | Low Fuel Level Shutdown | Shutdown | Add fuel; restart (switch OFF, then ON) |
| 00020 | Maximum Compressor Alarms | Shutdown | Report and repair immediately |
| 00021 | Tech Reset | Shutdown | Report and repair immediately |
| 00022 | Low Suction Superheat | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00023 | Over Current | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00024 | Compression Ratio | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00027 | High Suction Pressure | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00028 | Low Delta | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00029 | Check Heat Cycle | Alarm only | Reset (switch OFF, then ON); report if it returns |
Startup / Engine Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 00030 | Failed to Run Minimum Time | Shutdown | Report and repair immediately |
| 00031 | Auto Start Fail | Shutdown | Report and repair immediately |
| 00034 | Engine Failed to Stop | Alarm only | Move the fuel arm to the stop position (if equipped) or report and repair immediately |
| 00035 | Engine Failed to Crank | Shutdown | Report and repair immediately |
| 00036 | Low Coolant Temp | Alarm only | Check and repair at end of trip |
| 00037 | No Low Speed | Alarm only | Check and repair at end of trip |
| 00038 | No High Speed | Alarm only | Check and repair at end of trip |
| 00039 | Check Engine RPM | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00040 | Check Engine Preheat | Alarm only | Restart (switch OFF, then ON); report if it returns |
| 00041 | Engine Stalled | Shutdown | Restart (switch OFF, then ON); report if it returns |
Warning / Status Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 00051 | Alternator Check | Shutdown | Report and repair immediately |
| 00053 | Temp out of Range | Configurable | Reset (switch OFF, then ON); report if it returns |
| 00054 | Defrost Terminated by Time | Alarm only | Check and repair at end of trip |
| 00055 | Defrost Override | Alarm only | Check and repair at end of trip |
| 00056 | Check Evaporator Air Flow | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00057 | Door Open (Remote Switch 1) | Configurable | — |
| 00058 | Door Open (Remote Switch 2) | Configurable | Close all compartment doors; the unit should restart. If it stays shut down, repair immediately |
| 00059 | Data Recorder Memory Fail | Alarm only | Check and repair at end of trip |
| 00060 | Real Time Clock Failure | Alarm only | Check and repair at end of trip |
| 00061 | Door Open | Configurable | Close all compartment doors; the unit should restart. If it stays shut down, repair immediately |
| 00062 | Temp Out of Range Comp 2 | Configurable | Reset (switch OFF, then ON); report if it returns |
| 00063 | Temp Out of Range Comp 3 | Configurable | Reset (switch OFF, then ON); report if it returns |
| 00064 | Door Open Override | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00066 | Check Evap Sensor Group | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00068 | Remote Evap 1 not Configured | Alarm only | — |
Electrical Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 00073 | No A/C Power (Standby) | Configurable | Switch to diesel operation and repair |
| 00074 | Phase Reversed | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00075 | Compressor Motor Overload | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00076 | Condenser Motor Overload | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00077 | Evaporator Motor Over Load | Shutdown | Restart (switch OFF, then ON); report if it returns |
| 00078 | Check SV1 Solenoid Valve | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00079 | Check SV4 Solenoid Valve | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00080 | Check SV3 Solenoid Valve | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00081 | Check Fuel Heat Relay | Alarm only | Check and repair at end of trip |
| 00084 | Check Remote Alarm Light | Alarm only | Check and repair at end of trip |
| 00085 | Check UL-1 | Alarm only | Check and repair at end of trip |
| 00086 | Check UL-2 | Alarm only | Check and repair at end of trip |
| 00090 | Auto Fresh Air Exchange | Alarm only | Check and repair at end of trip |
| 00091 | Check Heater Contactor 1 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00092 | Check Heater Contactor 2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00093 | Check Prestart | Alarm only | Report and repair immediately |
| 00094 | Check Compressor Contactor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00095 | Check Condenser Motor Contactor 1 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00096 | Check Generator Contactor | Shutdown | Reset (switch OFF, then ON); report if it returns |
| 00097 | Check Liquid Solenoid Valve (SV2) | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00098 | Check High Temp Thermostat | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00100 | Overload/Ground Fault | Shutdown | Report and repair immediately |
| 00101 | Evap Motor Overload C2 | Shutdown | Report and repair immediately |
| 00102 | Evap Motor Overload C3 | Shutdown | Report and repair immediately |
| 00103 | Check C2 Heater 1 Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00104 | Check C2 Heater 2 Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00105 | Check C3 Heater 1 Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00106 | Check C3 Heater 2 Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00109 | Check Evaporator Contactor Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00110 | Check C2 Evaporator Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00111 | Check C3 Evaporator Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00114 | Check LIV Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00121 | Check Ambient Air Sensor | Alarm only | Check and repair at end of trip |
| 00122 | Check Return Air Sensor | Alarm only | If shut down, repair immediately; otherwise report and repair at end of trip |
| 00123 | Check Supply Air Sensor | Alarm only | — |
| 00124 | Check Defrost Termination Sensor | Alarm only | Check and repair at end of trip |
| 00125 | Check Discharge Temp Sensor | Alarm only | Check and repair at end of trip |
| 00126 | Low Fuel Alarm | Alarm only | Check and repair at end of trip |
| 00127 | Check Suction Temp Sensor | Alarm only | Check and repair at end of trip |
| 00128 | Low Unbalanced AMP | Alarm only | Check and repair at end of trip |
| 00129 | Check Coolant Temp Sensor | Alarm only | Check and repair at end of trip |
| 00130 | Check RPM Sensor | Alarm only | If shut down, repair immediately; otherwise report and repair at end of trip |
| 00131 | Check Evaporator Outlet Sensor | Alarm only | Check and repair at end of trip |
| 00132 | Check Defrost Termination Sensor | Alarm only | Check and repair at end of trip |
| 00133 | Check Remote Sensor 1 | Alarm only | Check and repair at end of trip |
| 00134 | Check Remote Sensor 2 | Alarm only | Check and repair at end of trip |
| 00135 | Check Remote Sensor 3 | Alarm only | Check and repair at end of trip |
| 00136 | Check C2 Supply Air Sensor | Alarm only | Check and repair at end of trip |
| 00137 | Check C2 Return Air Sensor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00138 | Check C3 Return Air Sensor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00139 | Check C2 Defrost Termination Sensor | Alarm only | Check and repair at end of trip |
| 00140 | Check C3 Defrost Termination Sensor | Alarm only | Check and repair at end of trip |
Pretrip Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 00141 | Pretrip Aborted by User | Alarm only | Report and repair immediately |
| 00143 | Check Clutch Circuit | Alarm only | Report and repair immediately |
| 00144 | Check UL1 Circuit | Alarm only | Report and repair immediately |
| 00145 | Check Speed Circuit | Alarm only | Report and repair immediately |
| 00146 | Check C2 Heater 1 Circuit | Alarm only | Report and repair immediately |
| 00147 | Check C2 Heater 2 Circuit | Alarm only | Report and repair immediately |
| 00148 | Check SV 1 Circuit | Alarm only | Report and repair immediately |
| 00150 | Check SV 4 Circuit | Alarm only | Report and repair immediately |
| 00151 | Check Engine Preheat Circuit | Alarm only | Report and repair immediately |
| 00152 | Check FSA Circuit | Alarm only | Report and repair immediately |
| 00153 | Check Return Air Sensor | Alarm only | Report and repair immediately |
| 00154 | Check Supply Air Sensor | Alarm only | Report and repair immediately |
| 00155 | Check Coolant Temp Sensor | Alarm only | Report and repair immediately |
| 00157 | Check Battery Circuit | Alarm only | Report and repair immediately |
| 00158 | Check Ambient Air Sensor | Alarm only | Report and repair immediately |
| 00159 | Check Defrost Termination Sensor | Alarm only | Report and repair immediately |
| 00160 | Check Discharge Temp Sensor | Alarm only | Report and repair immediately |
| 00161 | Check Suction Temp Sensor | Alarm only | Report and repair immediately |
| 00162 | Check Auto Fresh Air | Alarm only | Report and repair immediately |
| 00163 | Check C3 Heater 1 Circuit | Alarm only | Report and repair immediately |
| 00164 | Check UL 2 Circuit | Alarm only | Report and repair immediately |
| 00165 | Cannot Pump Down | Alarm only | Report and repair immediately |
| 00166 | Check C2 Supply Air Sensor | Alarm only | Report and repair immediately |
| 00167 | Check C3 Heater 2 Circuit | Alarm only | Report and repair immediately |
| 00168 | Cool LSV2 | Alarm only | Report and repair immediately |
| 00169 | Pre-Trip Economizer Circuit Alarm | Alarm only | Report and repair immediately |
| 00170 | Check LIV Circuit | Alarm only | Report and repair immediately |
| 00171 | System Not Equalized | Alarm only | Report and repair immediately |
| 00172 | Check Bypass | Alarm only | Report and repair immediately |
| 00173 | Check Economizer Circuit | Alarm only | Report and repair immediately |
| 00174 | No Low Speed | Alarm only | Report and repair immediately |
| 00175 | No High Speed | Alarm only | Report and repair immediately |
| 00176 | Cool LSV3 | Alarm only | Report and repair immediately |
| 00177 | Check Evaporator Superheat | Alarm only | Report and repair immediately |
| 00178 | Check UL 1 | Alarm only | Report and repair immediately |
| 00179 | Check LIV | Alarm only | Report and repair immediately |
| 00180 | Check SMV | Alarm only | Report and repair immediately |
| 00181 | Check SV 4 | Alarm only | Report and repair immediately |
| 00182 | Check SV 1 | Alarm only | Report and repair immediately |
| 00183 | Check SV 3 | Alarm only | Report and repair immediately |
| 00184 | Check C2 Evaporator Fan | Alarm only | Report and repair immediately |
| 00185 | Check C3 Evaporator Fan | Alarm only | Report and repair immediately |
| 00186 | Check Evaporator Outlet Temp | Alarm only | Report and repair immediately |
| 00187 | Check Heater 1 Circuit | Alarm only | Report and repair immediately |
| 00188 | Check Heater 2 Circuit | Alarm only | Report and repair immediately |
| 00189 | Check Evaporator Fan Motor | Alarm only | Report and repair immediately |
| 00190 | Check Condenser Fan Motor 1 | Alarm only | Report and repair immediately |
| 00191 | Check UL 2 | Alarm only | Report and repair immediately |
| 00192 | Check SV 2 | Alarm only | Report and repair immediately |
| 00194 | High Suction Pressure | Alarm only | Report and repair immediately |
| 00195 | Low Suction Pressure | Alarm only | Report and repair immediately |
| 00196 | High Discharge Pressure | Alarm only | Report and repair immediately |
| 00197 | Check Clutch | Alarm only | Report and repair immediately |
| 00198 | Low Discharge Pressure | Alarm only | Report and repair immediately |
| 00199 | Check C2 RAT | Alarm only | Report and repair immediately |
| 00201 | Check UL 2 Cylinder | Alarm only | Report and repair immediately |
| 00202 | High Side Leak | Alarm only | Report and repair immediately |
| 00203 | Check Discharge Check Valve | Alarm only | Report and repair immediately |
| 00204 | Low Suction Pressure | Shutdown | Report and repair immediately |
| 00205 | Check Defrost Termination Sensor | Alarm only | Report and repair immediately |
| 00206 | Check Condenser Fan Motor 1 Circuit | Alarm only | Report and repair immediately |
| 00207 | Check Compressor Contactor Circuit | Alarm only | Report and repair immediately |
| 00208 | Check Generator Contactor Circuit | Alarm only | Report and repair immediately |
| 00209 | Check Standby Contactor Circuit | Alarm only | Report and repair immediately |
| 00210 | Check C3 RAT | Alarm only | Report and repair immediately |
| 00211 | Check C2 Defrost Termination Sensor | Alarm only | Report and repair immediately |
| 00212 | Check C3 Defrost Termination Sensor | Alarm only | Report and repair immediately |
| 00217 | Check Electric Fuel Pump Circuit | Alarm only | Report and repair immediately |
| 00218 | Check Electric Heater for Compartment 1 | Alarm only | Report and repair immediately |
| 00219 | Check Electric Heater for Compartment 2 | Alarm only | Report and repair immediately |
| 00220 | Check Electric Heater for Compartment 3 | Alarm only | Report and repair immediately |
Maintenance Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 00223 | Maintenance Hour Meter-Total Diesel | Alarm only | Check and repair at end of trip |
| 00224 | Maintenance Hour Meter-Total Standby | Alarm only | Check and repair at end of trip |
| 00225 | Maintenance Hour Meter-Total Switch | Alarm only | Check and repair at end of trip |
| 00226 | Maintenance Hour Meter 1 | Alarm only | Check and repair at end of trip |
| 00227 | Maintenance Hour Meter 2 | Alarm only | Check and repair at end of trip |
| 00228 | Maintenance Hour Meter 3 | Alarm only | Check and repair at end of trip |
| 00229 | Maintenance Hour Meter 4 | Alarm only | Check and repair at end of trip |
| 00230 | Maintenance Hour Meter 5 | Alarm only | Check and repair at end of trip |
Microprocessor Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 00232 | Non-Valid Setpoint | Shutdown | Reset (switch OFF, then ON); report if it returns |
| 00233 | Non-Valid Model Number | Shutdown | Reset (switch OFF, then ON); report if it returns |
| 00237 | Non-Valid Functional Parameter | Shutdown | Reset (switch OFF, then ON); report if it returns |
| 00238 | Non-Valid Configuration Parameter | Shutdown | Reset (switch OFF, then ON); report if it returns |
| 00242 | Discharge Pressure Transducer Calibration | Shutdown | Reset (switch OFF, then ON); report if it returns |
| 00243 | Suction Pressure Transducer Calibration | Shutdown | Reset (switch OFF, then ON); report if it returns |
| 00244 | Economizer Pressure Transducer Calibration | Shutdown | Reset (switch OFF, then ON); report if it returns |
| 00245 | Cannot Save Settings | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00246 | Eprom Write Failure | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 00248 | Configuration Error | Shutdown | Reset (switch OFF, then ON); report if it returns |
| 00255 | System Failure | Shutdown | Reset (switch OFF, then ON); report if it returns |
Alarms 2000–2999
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 02000 | Software Incompatibility | Shutdown | Report and repair immediately |
| 02001 | Rear Panel Shutdown | Shutdown | Report and repair immediately |
| 02002 | Low Discharge Superheat | Shutdown | Report and repair immediately |
| 02003 | Display Failure | Shutdown | Report and repair immediately |
| 02004 | Out of Range High | Shutdown | Report and repair immediately |
| 02005 | Coil Over Temp | Shutdown | Report and repair immediately |
| 02006 | Starter Output Failure | Shutdown | Report and repair immediately |
Startup / Engine Alarms 3000–3999
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 03000 | Motor Overload #1 | Shutdown | Report and repair immediately |
| 03001 | Throttle Position Sensor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 03002 | Check Clutch Slip | Shutdown | Report and repair immediately |
| 03003 | No medium speed | Alarm only | Reset (switch OFF, then ON); report if it returns |
Warning / Status Alarms 4000–4999
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 04000 | Door Open (Remote Switch 3) | Configurable | Reset (switch OFF, then ON); report if it returns |
| 04001 | Door Open (Remote Switch 4) | Configurable | Reset (switch OFF, then ON); report if it returns |
| 04002 | High Economizer Superheat | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 04004 | No Setpoint Change | Alarm only | Re-enter the setpoint |
| 04005 | No Setpoint Change Comp 2 | Alarm only | Re-enter the setpoint |
| 04006 | No Setpoint Change Comp 3 | Alarm only | Re-enter the setpoint |
| 04007 | Remote Evap 2 Not Configured | Alarm only | Report and repair immediately |
| 04008 | Remote Evap 3 Not Configured | Alarm only | Report and repair immediately |
| 04016 | Check EES | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 04017 | Main Micro Reset Blocked | Alarm only | Clears when the third-party download is complete |
Electrical Alarms 5000–5999
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 05002 | Check Fuel Pump Relay | Alarm only | Report and repair immediately |
| 05003 | Check Diesel/Electric Relay | Alarm only | Report and repair immediately |
| 05004 | Bad F8 Fuse | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05005 | Bad F10 Fuse | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05006 | Power Enable Fuse Alarm | Alarm only | Report and repair immediately |
| 05007 | F-3 Blown | Alarm only | Report and repair immediately |
| 05008 | Bad F10 Fuse | Alarm only | Report and repair immediately |
| 05009 | Check Standby Contactor 1 | Shutdown | Report and repair immediately |
| 05010 | Check Standby Contactor 2 | Shutdown | Report and repair immediately |
| 05011 | Check High Speed | Alarm only | Report and repair immediately |
| 05012 | Check ENCU Power | Alarm only | Report and repair immediately |
| 05013 | Check Clutch Circuit | Alarm only | Report and repair immediately |
| 05014 | Check Starter Circuit | Alarm only | Report and repair immediately |
| 05015 | Check Three Way Valve Circuit | Alarm only | Report and repair immediately |
| 05016 | Check Remote Light Bar | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05017 | Check Preheat Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05018 | Check PER Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05019 | Check CDCON 2 Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05020 | Check Heater Contactor 1 Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05021 | Check Heater Contactor 2 Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05022 | Check C2 High Temp Thermostat | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05023 | Check C3 High Temp Thermostat | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05024 | Standby Motor | Shutdown | Report and repair immediately |
| 05025 | Check Power Source Contactor | Shutdown | Report and repair immediately |
| 05026 | Check A/C Phase | Shutdown | Report and repair immediately |
| 05027 | Generator Overheat | Shutdown | Report and repair immediately |
| 05028 | Bad PM Fuse 2 | Shutdown | Report and repair immediately |
| 05029 | Bad PM Fuse 3/5/7 | Alarm only | Report and repair immediately |
| 05030 | Bad PM Fuse 4 | Shutdown | Report and repair immediately |
| 05031 | Bad PM Fuse 10 | Shutdown | Report and repair immediately |
| 05032 | Bad PM Fuse 11 | Shutdown | Report and repair immediately |
| 05033 | Check PER Circuit | Shutdown | Report and repair immediately |
| 05034 | Check PER Contacts | Shutdown | Report and repair immediately |
| 05035 | EVXV Fault | Alarm only | Report and repair immediately |
| 05036 | ECXV Fault | Alarm only | Report and repair immediately |
| 05037 | SMV Fault | Alarm only | Report and repair immediately |
| 05038 | Compartment 2 EVXV1 Fault | Alarm only | Report and repair immediately |
| 05039 | Compartment 2 EVXV2 Fault | Alarm only | Report and repair immediately |
| 05040 | Compartment 3 EVXV1 Fault | Alarm only | Report and repair immediately |
| 05041 | Compartment2 EVXV2 Fault | Alarm only | Report and repair immediately |
| 05042 | Auxiliary Battery Voltage High | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05043 | Auxiliary Battery Voltage Low | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05044 | Stepper Board Voltage Low | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 05045 | Inverter Contactor Alarm | Alarm only | Report and repair immediately |
| 05046 | DC Battery Contactor Alarm | Alarm only | Report and repair immediately |
| 05047 | Inverter output alarm | Alarm only | Report and repair immediately |
| 05048 | Check liquid SV1 | Alarm only | Report and repair immediately |
| 05049 | Check liquid SV2 | Alarm only | Report and repair immediately |
| 05050 | Check liquid SV3 | Alarm only | Report and repair immediately |
| 05051 | Check hot gas SV1 | Alarm only | Report and repair immediately |
| 05052 | Check hot gas SV2 | Alarm only | Report and repair immediately |
| 05053 | Check hot gas valve SV3 | Alarm only | Report and repair immediately |
| 05054 | Check MHV | Alarm only | Report and repair immediately |
| 05055 | Check Flash Relay | Alarm only | Report and repair immediately |
| 06000 | Condenser Fan 2 Overload | Shutdown | Report and repair immediately |
| 06002 | Compressor Protect Mode | Shutdown | Reset (switch OFF, then ON); report if it returns |
| 06003 | Check Evaporator Fan 2 Circuit | Alarm only | Report and repair immediately |
| 06004 | Check Defrost Drain Heater Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 06005 | Check Electric/Water Heat Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 06006 | Defrost Drain Heater C2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 06007 | Defrost Drain Heater C3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
Sensor Alarms 7000–7999
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 07000 | Check Economize Temp Sensor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07001 | Check Economizer Pressure Transducer | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07002 | Check C3 Supply Air Sensor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07003 | Check C2 Evaporator Outlet Sensor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07004 | Check C3 Evaporator Outlet Sensor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07005 | Check Engine OP Switch (TDO) | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07006 | Check Suction Pressure Transducer | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07007 | Compressor A/C Current | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07008 | Check Redundant RAT | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07009 | RAT Temp Sensor Out of Range | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07010 | Check Redundant SAT | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07011 | Check Evaporator Pressure Sensor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07012 | Check Economizer Pressure Sensor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07013 | Check Compressor Discharge Pressure Sensor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07014 | Check C2 Redundant RAT | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07015 | C2 RAT Temp Sensor Out of Range | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 07016 | Compressor High Power | Alarm only | Reset (switch OFF, then ON); report if it returns |
Pretrip Alarms 11000–17999
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 11000 | Check Condenser Fan Motor 2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11001 | Check Standby Contactor Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11002 | Check Hot Gas Valve (Supra) | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11003 | Check Evap Fan 1 & 2 (Supra) | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11004 | Check Evap Fan 3 (Supra) | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11005 | Check Defrost Drain Heater 2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11006 | Check Defrost Drain Heater 3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11007 | Check Hot Gas Valve 2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11008 | Check Hot Gas Valve 3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11009 | Check Main Heat Valve | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11010 | Check Liquid Valve 1 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11011 | Check Liquid Valve 2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11012 | Check Liquid Valve 3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 11017 | Check VFD | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 12000 | Check Supply Air Sensor C3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 12001 | Check EVOT Sensor C2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 12002 | Check EVOT Sensor C3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 12003 | Check Economizer Sensor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 13000 | Check Condenser Fan 2 Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 13001 | Check Hot Gas Valve Circuit (Supra) | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 14000 | Check Evap 1 Superheat C2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 14001 | Check Evap 2 Supreheat C2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 14003 | Check Evap 2 Supreheat C3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 14004 | Check Hot Gas Valve for Compartment 1 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 14005 | Check Hot Gas Valve 2 for Compartment 2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 14005 | Check Hot Gas Valve for Compartment 3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 14006 | Check Hot Gas Valve 3 for Compartment 3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 14007 | Check Main Heat Valve | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 14008 | Check Liquid Valve for Compartment 1 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 14009 | Check Liquid Valve 2 for Compartment 2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 14010 | Check Liquid Valve 3 for Compartment 3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 15001 | No Medium Speed (Supra) | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 15005 | Check Very High Speed RPM | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 16000 | Check High Pressure Switch | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 16001 | No Alarm 13 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 17000 | Check EES Air Control Valve | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 17001 | Check EES Fueling System | Alarm only | Reset (switch OFF, then ON); report if it returns |
GTD Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 20100 | No communication from Micro to Display | Alarm only | Report and repair immediately |
| 20101 | No communication from Micro to Remote Display | Alarm only | Report and repair immediately |
MMB Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 21100 | No Comm from Micro to any Module | Shutdown | Report and repair immediately |
INPBD1 Alarms (Input Board)
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 22100 | No Comm from Micro to Input Board 1 | Shutdown | Report and repair immediately |
| 22101 | Input Voltage Low to Input Board 1 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 22102 | Input Voltage High to Input Board 1 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 22103 | Configuration Error Input Board 1 | Shutdown | Report and repair immediately |
| 22400 | MSM1 Input CAN Fail | Shutdown | Report and repair immediately |
| 22401 | MSM1 Input Voltage Low | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 22402 | MSM1 Input Voltage High | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 22403 | MSM1 Input Lost Configuration | Shutdown | Report and repair immediately |
| 22500 | No Comm from MSM2 to Input Board | Shutdown | Report and repair immediately |
| 22501 | Sensor Input Voltage Low to MSM2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 22502 | Sensor Input Voltage High to MSM2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 22503 | Configuration Error MSM2 | Shutdown | Report and repair immediately |
| 22800 | No Comm from MCA to Input Board | Shutdown | Report and repair immediately |
| 22801 | Sensor Input Voltage Low to MCA | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 22802 | Sensor Input Voltage High to MCA | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 22803 | Configuration Error MCA | Shutdown | Report and repair immediately |
OTBD1 Alarms (Output Board)
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 23100 | No Comm from Micro to Output Board 1 | Shutdown | Report and repair immediately |
| 23101 | Configuration Error Output Board 1 | Shutdown | Report and repair immediately |
| 23800 | PM CAN Fail | Shutdown | Report and repair immediately |
| 23801 | Power Module Lost Configuration | Shutdown | Report and repair immediately |
| 23803 | Configuration Error TPC | Shutdown | Report and repair immediately |
CCB Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 24100 | No Comm for CCB1 | Shutdown | Report and repair immediately |
| 24101 | Sensor Input Voltage Low to CCB1 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 24102 | Sensor Input Voltage High to CCB1 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 24103 | CCB Lost Configuration | Shutdown | Report and repair immediately |
| 24200 | CCB CAN Fail | Shutdown | Report and repair immediately |
| 24201 | Sensor Input Voltage Low to CCB2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 24202 | Sensor Input Voltage High to CCB2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 24203 | CCB Lost Configuration | Shutdown | Report and repair immediately |
| 24300 | No Comm for CCB3 | Shutdown | Report and repair immediately |
| 24301 | Sensor Input Voltage Low to CCB3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 24302 | Sensor Input Voltage High to CCB3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 24303 | CCB3 Lost Configuration | Shutdown | Report and repair immediately |
| 24400 | No Comm for CCB4 | Shutdown | Report and repair immediately |
| 24401 | Sensor Input Voltage Low to CCB4 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 24402 | Sensor Input Voltage High to CCB4 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 24403 | CCB4 Lost Configuration | Shutdown | Report and repair immediately |
STP Alarms (Stepper Valve Module)
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 25100 | No Comm from Stepper 1 | Shutdown | Report and repair immediately |
| 25101 | Stepper 1 Over Current | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25102 | Input Voltage Out of Range Stepper 1 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25200 | No Comm from Stepper 2 | Shutdown | Report and repair immediately |
| 25201 | Stepper 2 Over Current | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25202 | Input Voltage Out of Range Stepper 2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
ENCU1 Alarms (Engine Control Unit)
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 25300 | No Comm from Stepper 3 | Shutdown | Report and repair immediately |
| 25301 | Stepper 3 Over Current | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25302 | Input Voltage Out of Range Stepper 3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25400 | No Comm from Stepper 4 | Shutdown | Report and repair immediately |
| 25401 | Stepper 4 Over Current | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25402 | Input Voltage Out of Range Stepper 4 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25500 | Tri-Stepper CAN Fail | Shutdown | Report and repair immediately |
| 25501 | Tri-Stepper Over Current | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25502 | Tri-Stepper Input Voltage | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25503 | Tri-Stepper Lost Config | Shutdown | Report and repair immediately |
| 25600 | No Comm from Tri-Stepper 2 | Shutdown | Report and repair immediately |
| 25601 | Tri-Stepper 2 Over Current | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25602 | Input Voltage Out of Range Tri-Stepper 2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25603 | Configuration Error Tri-Stepper 2 | Shutdown | Report and repair immediately |
| 25800 | No Comm from SIOB | Shutdown | Report and repair immediately |
| 25801 | SIOB Over Current | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25802 | Input Voltage Out of Range SIOB | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 25803 | Configuration Error SIOB | Shutdown | Report and repair immediately |
| 26100 | No Comm from ENCU | Shutdown | Report and repair immediately |
| 26101 | Engine Overheat | Engineering event | — |
| 26102 | Water Temp Sensor Low | Engineering event | — |
| 26103 | Water Temp Sensor High | Engineering event | — |
| 26104 | Battery Voltage High | Engineering event | — |
| 26105 | Engine Overrun (Kubota) | Shutdown | Report and repair immediately |
| 26106 | Sensor Supply Voltage to ENCU Low | Shutdown | Report and repair immediately |
| 26108 | Rack Position Sensor Abnormal | Engineering event | — |
| 26109 | Check Actuator (Kubota) | Shutdown | Report and repair immediately |
| 26110 | Check RPM Sensor (Kubota) | Shutdown | Report and repair immediately |
| 26162 | Water in Fuel | Alarm only | Report and repair immediately |
EES Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 26200 | No Comm form EES Module | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26201 | EES Service Required | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26202 | EES High Back Pressure | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26203 | EES Low Back Pressure | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26204 | EES ECU Low Voltage | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26205 | EES Filter Inlet Temp | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26206 | EES Check Fuel Pump Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26207 | EES Check Air Control Valve | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26208 | EES Check Fuel Injection Circuit | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26209 | EES Filter Outlet Temp | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26210 | EES Exhaust Inlet Temp | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26211 | EES ECU Output Failure | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26212 | EES ECU Log Failure | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26213 | EES ECU Clock Failure | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26214 | EES ECU Temp Low | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26215 | EES ECU Temp High | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26216 | EES No Temp Rise | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26217 | EES System Failure | Shutdown | Report and repair immediately |
| 26218 | EES System Overtemp | Shutdown | Report and repair immediately |
| 26219 | EES Temp Sensor Drift | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26220 | EES Back Pressure Exceeded | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26221 | EES Frequent Regeneration | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 26222 | EES Back Pressure Offset Exceeded | Alarm only | Reset (switch OFF, then ON); report if it returns |
Engine Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 26300 | ENCU Comm Failure | Shutdown | Report and repair immediately |
| 26301 | ENCU Alarm (PCODE/SPN) | Shutdown | Report and repair immediately |
| 26302 | ENCU Alarm (PCODE/SPN) | Alarm only | Report and repair immediately |
| 26500 | Incompatible ENCU | Shutdown | Report and repair immediately |
Communication Alarms
| Code | Alarm | Response | What to do |
|---|---|---|---|
| 27100 | Loss of Communication to Comm Module | Shutdown | Report and repair immediately |
| 27200 | Loss of Communication to Optional Comm Module | Alarm only | Report and repair immediately |
| 28001 | No Comm from Fuel Sensor | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 28002 | No Comm from Door Switch | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 28003 | Invalid 3rd Party Door Switch | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 28004 | Invalid 3rd Party REMS1 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 28005 | Invalid 3rd Party REMS2 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 28006 | Invalid 3rd Party REMS3 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 28007 | Invalid 3rd Party REMS4 | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 28008 | No Comm From Fuel Flow Meter | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 29000 | Alternator Electric Issue | Shutdown | Report and repair immediately |
| 29001 | Alternator High Temp | Shutdown | Report and repair immediately |
| 29002 | Alternator Belt Broken | Shutdown | Report and repair immediately |
| 29003 | Alternator Belt Slip | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 29004 | LIN Comm Error | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 29005 | LIN Comm Timeout | Alarm only | Reset (switch OFF, then ON); report if it returns |
| 29006 | No Comm to Alternator | Shutdown | Report and repair immediately |
| 29007 | Power Frequency | Alarm only | Reset (switch OFF, then ON); report if it returns |
Symptom Troubleshooting Guide
How to use the list above: find the code shown on the MessageCenter, check whether it shuts the unit down, and follow the recommended action. When an alarm keeps returning after the sensor, wiring or component it names has been checked — or when it is a microprocessor, NO COMM or board alarm — the controller module itself may be at fault.
| Symptom | Likely Causes | How We Repair It |
|---|---|---|
| An alarm returns after restarting the unit | The condition is still present: the sensor, circuit or system the alarm names | Record the alarm before clearing it, as Carrier recommends, then check the item it names. Report every reactivation |
| Microprocessor alarms (00232–00255) that will not clear | Invalid or unwritable data in the main microprocessor memory, or software that needs an update | Re-enter the setting and update the software. If the alarm remains, the main microprocessor module needs repair |
| NO COMM alarms (21100–25100) | The main microprocessor lost a module on the CAN bus: wiring, connector pins, or the module itself | Look at how many NO COMM alarms are active: several point to the wiring or the main microprocessor, a single one points to the module it names |
| Sensor or circuit alarms that return after the part was replaced | Wiring, or the controller’s input or output circuit for that sensor or component | Check the wiring end to end. If it is good, the controller input or driver is the next suspect — repairable at component level |
Frequently Asked Questions
What is the difference between a Shutdown and an Alarm-only code?
A shutdown alarm stops the unit; an alarm-only code lets it keep running while it warns you. Carrier marks some alarms as configurable, so they can be set as either one.
How do I clear an APX alarm?
Carrier recommends recording every alarm before clearing it. Alarms that say to reset or restart are cleared by placing the START/RUN-OFF switch in OFF and then back in START/RUN; if the condition is still there, the alarm returns.
Does this list apply to the X4 Series 8?
X4 7300 / 7500 Series 8 units (serial UAJ91657524 and later) also use the APX control system, but their microprocessor hardware is different: a Microprocessor Stepper Module (MSM) and a Power Module (PM) instead of separate main microprocessor and stepper valve modules. Some alarms change with the software revision, so check your unit’s manual.
Which alarms point to the controller?
Mainly the microprocessor alarms (00232–00255), the NO COMM and module alarms (21100–25100, INPBD1, OTBD1, STP) and circuit alarms that keep returning after the wiring and the component check good. We repair the APX main microprocessor and the stepper valve module at component level.
1-Year Warranty
Every repair ships back bench-tested, with a 1-year warranty on the components we repaired or replaced, plus 15 days of coverage for any other functional problem after delivery.
Start Your Repair NowWhy Choose DCF?
- $150 Diagnostic — Fully Waived When We Complete the Repair
- 7–15 Business-Day Standard Turnaround
- Component-Level Repair
- Miami-Based Facility
- Standard ground return shipping paid by DCF